Generation Capacity Limits

There are limits to how much generation Horizon Utilities' distribution system can accommodate. The table below provides minimum total generation capacity limits for feeders in Horizon Utilities' distribution system. For any specific feeder, the total generation capacity limit will be equal to or greater than the minimum limits in the table below. Exact total generation capacity limits for specific feeders can be determined through the preliminary assessment stage.

Feeder Nominal Voltage (kV) Generation Capacity Limit
(A) (MVA)
4.16 150 1.1
8.32 130 1.9
13.86 150 3.6
27.6 330 15.8